久久影视一区-久久影视在线观看-久久影院精品-久久永久免费-亚洲天天在线-亚洲天天综合

  Location: Home > Products >  Automatic Fire Alarm and Linkage Control System >  Modules
Products
Broadcast System Repeater Controller Modules Sound and Light Alarm Detector The Internet Manual Call Point Telephone System Power Supply Explosion-Proof Series
Input / Output Module(J-EI6042N)
Product Overview:

(1)Double input and double output ports. They can be programmed separately. They can be used separately or in combination.

(2)The signal input line from the device, the circuit breaker fault and the module output line fault can be detected.

.Electronic coding, unique ID, online addressing, automatic login, easy installation and debugging.

.The signal input line from the device, the circuit breaker fault and the module output line fault can be detected.

.24V disconnection fault can be detected.

.New plug-in structure, easy installation and wiring.


Bus operating voltage: 24V pulsating voltage        

Line: two bus (non polarity)Use

Ambient temperature: -10°C ~ +50°C        

Use ambient humidity: < 95RH (without dew)

24V power supply: DC 24V±1015% DC, 24V power (non-polar)

Monitor current: 0.4mA (bus); < < 5.0mA (DC24V)       

Action current: < 3.6mA (bus); < 50mA (DC24V)        

Relay contact: two groups normally open, normally closed, DC30V/1A shell

Protection level: IP30

Bus length: 2000m

Load resistance: 1/4W 47K


Back
Contact Us
eifire@eifire.com
400-0552-119
Contact Us400-0552-119
Follow Us Follow Us